Product Information
ManufacturerLEM
Manufacturer Part NoDVL 1500-UICopy
Manufacturer Standard Lead Time14 weeks
Order Code2664164
Product RangeDVL-UI Series
Technical Datasheet
Transducer FunctionVoltage Transformer
Supply Voltage Min-13.5V
Measured VoltageAC, DC, Pulsed
Supply Voltage Range± 13.5V to ± 26.4V
Supply Voltage Max26.4V
Accuracy %0.5%
Primary Voltage Nom1.5kV
Accuracy± 1%
Secondary Signal Type4mA to 20mA
Sensor Output TypeAnalog
Input Current25mA
External Depth100mm
Sensor MountingPanel Mount
Output Current Max21mA
Operating Temperature Min-40°C
Operating Temperature Max85°C
Linearity %0.5%
Product RangeDVL-UI Series
SVHCNo SVHC (25-Jun-2025)
Product Overview
DVL 1500-UI is a DVL-UI series voltage transducer for the electronic measurement of voltage: DC, pulsed, with galvanic separation between the primary and the secondary circuit. Standards include EN 50155: 2021, EN 50178: 1997, EN 50124-1: 2017, EN 50121-3-2: 2016, UL 508: 2013. Applications include substations and trackside.
- 4-20mA output
- Input and output connections with M5 studs
- Compatible with AV 100 family
- Low consumption and low losses, compact design
- Good behaviour under common mode variations, excellent accuracy (offset, sensitivity, linearity)
- Good delay time, low temperature variation, high immunity to external interferences
- 1500V primary nominal DC voltage at TA = 25°C, ±UC = ±24V, RM = 100 ohm
- 100ms rise time of UC (10 ‒ 90%) at TA = 25°C, ±UC = ±24V, RM = 100 ohm
- 30mA max current consumption at UC = ±24V at UP = 0V
- Ambient operating temperature range from -40 to 85°C
Technical Specifications
Transducer Function
Voltage Transformer
Measured Voltage
AC, DC, Pulsed
Supply Voltage Max
26.4V
Primary Voltage Nom
1.5kV
Secondary Signal Type
4mA to 20mA
Input Current
25mA
Sensor Mounting
Panel Mount
Operating Temperature Min
-40°C
Linearity %
0.5%
SVHC
No SVHC (25-Jun-2025)
Supply Voltage Min
-13.5V
Supply Voltage Range
± 13.5V to ± 26.4V
Accuracy %
0.5%
Accuracy
± 1%
Sensor Output Type
Analog
External Depth
100mm
Output Current Max
21mA
Operating Temperature Max
85°C
Product Range
DVL-UI Series
Technical Docs (3)
Legislation and Environmental
Country of Origin:
Country in which last significant manufacturing process was carried outCountry of Origin:Bulgaria
Country in which last significant manufacturing process was carried out
Country in which last significant manufacturing process was carried outCountry of Origin:Bulgaria
Country in which last significant manufacturing process was carried out
Tariff No:85043121
US ECCN:EAR99
EU ECCN:NLR
RoHS Compliant:Yes
RoHS
RoHS Phthalates Compliant:Yes
RoHS
SVHC:No SVHC (25-Jun-2025)
Download Product Compliance Certificate
Product Compliance Certificate
Weight (kg):.29